2 - 15

6 FUJI PLC

6

Available Memory

*

The current values of the timer and counter are indicated with TN/CN for purposes of

convenience in the table above. (The actual value is T/C.)

Set the memory to the extent of the memory range of each PLC model.

Use TYPE number to assign indirect memory for macro programs.

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-422

Wiring Diagram 1

*

Recommended cable : O-VCTF-SS, 2C 0.75 mm

2

, made by Chyugoku Densen

Memory

TYPE

Remarks

D

(data register)

0

R

(link register)

1

M

(internal relay)

2

WM as word device

K

(latch relay)

3

WK as word device

X

(input relay)

4

WX as word device

Y

(output relay)

5

WY as word device

W

(file register)

6

TN

(timer/current value)

7

Read only

*

CN

(counter/current value)

8

Read only

*

T

(timer/contact)

9

C

(counter/contact)

10

Z

(special register)

12

V

(special relay)

13

WV as word device

D-sub 25pin(Male: )

FG

1

12

13

24

25

PLC

SG

SG

7

Max. 500 m

POD (CN1)

+SD

-SD

+RD

-RD

+

-

*

Use twist shielded cables.