7 wiring, Wiring -19, Wiring – Fujitronic Programmable Operation Display UG520H-x User Manual

Page 28: Electrical wiring, Twisted

Advertising
background image

1 - 19

Electrical Wiring

Connects the cable for power supply to TB1 on the rear side of UGx20.

Wiring

7

Insulation transformer

or

Stabilized transformer

1.25mm

2

Power Supply

twisted

to UG520/UG420

When TB1 is used for wiring, refer to the following table.
The power source used must be within the allowable voltage fluctuation.
Use a power source with low noise between the cables or ground and the cable.
Use as thick a power cable as possible to minimize any drop in voltage.
Keep cables of 100V AC and 24V DC sufficiently away from high-voltage, large-current cables.

Notes on Usage of UG520/UG420 100-200V AC Specifications

Generally, an isolating transformer improves noise resistance. However, if the display unit is far away

from the secondary port of the transformer and noise gets mixed in, an isolating transformer becomes

unnecessary.

If any power voltage fluctuation caused by noise is expected, it is recommended that a voltage stabilizer

be used.

Screw Screw Size

M3.5

Torque (N • m)

Clamp Terminal (Unit : mm)

0.5

7.0MAX

7.0MAX

M3.5

0.5

8.0MAX

8.0MAX

Type

UG320/UG221/UG220

UG520/UG420

24V DC

(

+

)

(-)

TB1

Power supply
24V

±

10% DC

Earth

Power supply
100-200VAC

L

N

NC

TB1

Earth

CN2

C

N

1

MJ2 MJ1

DC24V

(+)

(-)

CN2

MJ1

MJ2

CN

1

100-

240VAC

L

N

NC

24VDC

Power supply
24V

±

10% DC

+

-

NC

TB1

Earth

Type : 100-200V AC

Type : 24V DC

UG320/UG221/UG220

UG520/UG420

7 Wiring

Caution

Do not remove the dust-proof seal till you finish wiring in the panel. If the seal is removed, conductor chips or other

foreign matter may enter the device to cause failure.

When you finished wiring in the panel, be sure to remove the dust-proof seal.