Fujitronic Programmable Operation Display UG520H-x User Manual

Page 50

Advertising
background image

1 - 41

Signal

UG00P-DI

UG port

FG

+SD

-SD

+RD

-RD

SG

*

Use twist shielded cable.

Signal

Pin No.

+RxD

+TxD

+DSR

+DTR

1

2

3

4

5

SG

7

-RxD

15

-TxD

16

-DSR

17

-DTR

18

20

21

Signal

FG

+SD

-SD

+RD

-RD

SG

RD terminal resistance

(ON)

RD/SD terminal resistance

(ON)

RD/SD terminal resistance

(ON)

Signal

FG

+SD

-SD

+RD

-RD

SG

POD + UG00P-TC

POD + UG00P-TC

POD + UG00P-TC

Signal

FG

+SD

-SD

+RD

-RD

SG

RD terminal resistance

(ON)

RD/SD terminal resistance

(ON)

Signal

FG

+RxD

-RxD

+TxD

-TxD

SG

Link unit

Signal

FG

+SD

-SD

+RD

-RD

SG

RD/SD terminal resistance

(ON)

Signal

FG

+SD

-SD

+RD

-RD

SG

*

Use twist shielded cable.

POD + UG00P-TC

POD + UG00P-TC

POD + UG00P-TC

16 Connection

When multiple POD are connected to a link unit of PLC, use the terminal converter (UG00P-TC), the

optional equipment made by Fuji Electric. Co., Ltd. for RS-485 connection.

Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.

Short-circuit between +RD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.

When multiple POD are connected directly to MITSUBISHI’s QnA CPU port, the optional equipment,

UG00P-DI is required. Also, the use of the optional cable, MB-CPUQT which is to connect UG00P-TC on

POD side to UG00P-DI on QnA CPU port side, is recommended.

Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.

Short-circuit between +RD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.

*

An n-to-1 system can be also configured using optional interface units (UG03I (02I)-S, -T, -J, -E(2), -C, or -P).

For the details, refer to the User’s Manual of each optional interface unit.