24 toyopuc plc, Toyopuc plc -67, Toyopuc plc – Fujitronic Programmable Operation Display UG520H-x User Manual

Page 136

Advertising
background image

2 - 67

24 TOYOPUC PLC

TOYOPUC PLC

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Set the [Trans. Mode] for [Detail] in the [Comm. Parameter].

· PC3J

: Select [Single Data Area] or [Split Data Area].

· L2/PC2 series

: Select [Single Data Area].

Switch Setting

Baud rate: 19200bps

24

Trans. Mode

Contents

Single Data Area

Data area is common.

Split Data Area

Divide each PLC device into a program file.

PLC

CMP-LINK

RS-422 [Wiring Diagram 1]

Select PLC Type

TOYOPUC

L2/PC2 Series
PC3J

Wiring Diagram

Link Unit

19200bps

Even

0

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

2

Port

Item

Setting of PLC

19200bps

Even

2

0

7

7

Comm. Parameter of POD

SW1

Switch

SW2

SW3

0

0

1

Setting

Contents

Station address (lower half)

Station address (upper half)

Baud rate
1 : 19200 2 : 9600 3 : 4800
4 : 2400 5 : 1200 6 : 600

SET2

Switch

SET3

Provided

Provided

Short bar

Contents

Data bit 7

Stop bit 2

Advertising