2 - 109

KEYENCE PLC • 2

(KZ-A500)

41

41 KEYENCE PLC

2

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

CPU modular port of KZ-A500

Link Unit KZ-L10

Set the port with the port setting switch, the terminating resistance with

terminator, and the baud rate/data bit/parity/stop bit with SET B dip switches.

For further information, refer to the communication specifications of KZ-L10.

PLC

Link Unit

Wiring Diagram

KZ-A500

Port 2

RS-232C [Wiring Diagram 3]

RS-422 [Wiring Diagram 4]

KZ-L10

CPU Modular Port

Port 1

RS-232C [Wiring Diagram 2]

Select PLC Type

MITSUBISHI

A series link

KZ-A500

CPU

RS-232C [Wiring Diagram 1]
RS-422 Cable made by KEYENCE [ KZ-C20 ]

+ Cable made by Fuji [ UG200C-M ]

9600bps

Odd

8

ON for RS-422

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

1

Terminal Resistor

Item

Setting of PLC

9600bps

0

Port

0

Odd

8

1

*

1

*

1 In case of RS-422, the baud rate is fixed at 9600bps.

Comm. Parameter of POD

19200bps

Even

7

ON for RS-422

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

1

Terminal Resistor

Item

Setting of PLC

19200bps

0

Port

0

Even

7

1

Comm. Parameter of POD