31 toshiba machine plc, Toshiba machine plc -90, Toshiba machine plc – Fujitronic Programmable Operation Display UG520H-x User Manual

Page 159: Tc200), Available plc communication setting

Advertising
background image

2 - 90

TOSHIBA MACHINE PLC

(TC200)

31

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows.

Available Memory

Set the memory to the extent of the memory range of each PLC model.

Use TYPE number to assign indirect memory for macro programs.

TC200

TC200

PLC

Port on a CPU unit

TCCMW
TCCMO

RS-232C [Wiring Diagram 1]

Select PLC Type

Link Unit

Wiring Diagram

Port

1

9600bps

Baud Rate

Item

Setting of PLC

1

9600bps

Comm. Parameter of POD

31 TOSHIBA MACHINE PLC

Memory

TYPE

Remarks

D

(register 1)

0

B

(register 2)

1

X

(input relay)

2

XW

as word device

Y

(output relay)

5

YW

as word device

R

(temporary storage)

6

RW

as word device

G

(extension temporary storage 1)

7

GW

as word device

H

(extension temporary storage 2)

8

HW

as word device

L

(latch)

9

LW

as word device

S

(shift register)

10

SW

as word device

E

(edge relay)

11

EW

as word device

P

(timer counter current value)

12

V

(timer counter set value)

13

T

(timer)

14

TW

as word device

C

(counter)

15

CW

as word device

A

(special auxiliary relay)

16

AW

as word device

Advertising