Notes on using UG00P-DI (Dual Port Interface)

As the UG00P-DI is powered by a CPU, check that the electric capacity of the CPU is at 5V (power

consumption: max. 350mA).

The distance between the CPU and the UG00P-DI should be as short as possible (max. 1 to 1.5m).

For wiring, take appropriate measures to eliminate noise.

Specify the value more than 150 (=1.5 sec) in [Time-out Time] of [Comm. Parameter] in case of

connecting POD to a UG00P-DI.

CPU

PLC

A6GPP, A7PHP, personal computer, etc.

GD

G

P

P

UG200C-G

Slide switch

1 • • • A series
2 • • • QnA series
3 • • • FX series

*

Note:
Be sure to turn the power off
when changing over of the
sliding switch.

POD

MITSUBISHI A/QnA
Series.

1 2 3

In case of direct connection with the
CPU port of A/QnA series,

plug the rear connector of UG00P-DI
in the CPU port, or use the cable
"UG200C-G" made by Fuji Electric.