Communication setting – Fujitronic Programmable Operation Display UG520H-x User Manual

Page 86

Advertising
background image

2 - 17

7 MITSUBISHI PLC

1

Port

Transmission
Control Mode

RS-232C

RS-422

MODE1

MODE5

Trans. Mode 1

Trans. Mode 1

19200bps

Even

7 (ASCII)

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

1

Sumcheck

Write while running

Terminal Resistor at Sender

Terminal Resistor at Receiver

Item

Setting of PLC

0

19200bps

Even

7

1

*

1

0 for both STATION x10 and x1

Comm. Parameter of POD

Provided (fixed)

Available (fixed)

Provided (fixed)

Provided (fixed)

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

A series link unit

*1 Mode 1: without CR/LF, Mode 4: with CR/LF

If [Trans. Mode 4] is selected from [Trans. Mode] in [Comm. Parameter] of the panel editor,

specify [MODE4] in case of RS-232C, or select [MODE8] in case of RS-422.

Q series link unit

Port

Transmission
Control Mode

RS-232C

RS-422

When QnA series link is connected:

MODE5 (Binary Mode) (fixed).

When QnH(Q) series link is connected:

MC Protocol Type 5 (fixed).

0 for both STATION X 10 and X1

19200bps

Even

8 (fixed)

Provided (fixed)

Available (fixed)

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

1

Sumcheck

Write while running

Item

Setting of PLC

0

19200bps

Even

1

Comm. Parameter of POD

Q00/Q01 CPU

When connecting the POD to the tool port of Q00 or Q01 CPU, it is neccessary to specify [serial

communication] setting on PLC parameter. Note on the following setting.

UG00S-CW

Select [QnH(Q) series link] in [PLC type].

GX Developer (Application software for programming MITSUBISHI PLCs)

1. Double click [PLC parameter].

2. Click the [Serial] tab menu of the [Qn(H) Parameter] dialog.

3. Check [Use serial communication] to specify communication parameters such as Baud rate,

Sum check, etc.