Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Available Memory

Set the memory to the extent of the memory range of each PLC model.

Use TYPE number to assign indirect memory for macro programs.

PLC

MX200/MX50

RS-232C [Wiring Diagram 1]

Select PLC Type

MX Series

Wiring Diagram

9600bps

1

Even

Even

1

Port

Baud Rate

Parity

Data Length

Stop Bit

Item

Setting of PLC

9600bps

8

8

1

1

Transmission

Code

Comm. Parameter of POD

Memory

TYPE

Remarks

R

(data register)

0

M

(auxiliary relay)

1

L

(latch relay)

2

X

(input relay)

3

Y

(output relay)

4

TP

(timer/current value)

5

TS

(timer/set value)

6

CP

(counte/current value)

7

CS

(counter/set value)

8

T

(timer/contact)

9

C

(counter/contact)

10

P

(link register)

11