19 matsushita plc, Matsushita plc -54, Matsushita plc – Fujitronic Programmable Operation Display UG520H-x User Manual

Page 123

Advertising
background image

2 - 54

Matsushita PLC

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

*

If a tool port (the ladder port for RS-232C) of FP0 is used, the range of PLC parameter setting is

limited as below. Adjust PLC parameter setting to comm. parameter setting of POD.

Baud rate

: 9600, 19200bps

Parity

: Odd (fixed)

Data bit

: 8 (7 can be selected. Normally 8.)

Stop bit

: 1 (fixed)

Port

19200bps

Even

7 (ASCII)

Baud Rate

Parity

Transmission

Code

Data Bit

Stop Bit

1

Transmission Control

Control Signal

Item

Setting of PLC

19200bps

Even

7

1

Comm. Parameter of POD

"0" for 10, "1" for

1

1

Computer link system (fixed)

Invalid (fixed)

FP1

FP0

FP3

FP5

FP10

RS-232C port
on a CPU unit

RS-232C port
on a CPU unit

AFP3462

AFP3463

AFP5462

AFP5462

RS-232C tool port
on a CPU unit

RS-232C cable made by Matsushita
AFC8513

PLC

Link Unit

Wiring Diagram

RS-232C [Wiring Diagram 1]

RS-232C [Wiring Diagram 1]

RS-422 [Wiring Diagram 4]

RS-232C [Wiring Diagram 1]

RS-422 [Wiring Diagram 4]

RS-232C [Wiring Diagram 1]

RS-232C [Wiring Diagram 1]

RS-232C [Wiring Diagram 1]

RS-232C [Wiring Diagram 3]

FP10S

RS-232C port
on a CPU unit

RS-232C port
on a CPU unit

AFP3462

AFP3463

RS-232C [Wiring Diagram 1]

Select PLC Type

MEWNET

FP2

RS-232C tool port
on a CPU unit

RS-232C cable made by Matsushita
AFC8513

RS-232C [Wiring Diagram 2]

RS-232C port
on a CPU unit