background image

2 - 89

30 TOSHIBA PLC

Available Memory

Set the memory to the extent of the memory range of each PLC model.

Use TYPE number to assign indirect memory for macro programs.

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-422

Wiring Diagram 1

D-sub 25pin(Male: )

FG

SG

2

PLC

D-sub 15pin(Male: )

3

4

RXA

TXA

CTSA

RTSA

5

SG

7

7

1

12

13

24

25

10

11

12

13

RXB

TXB

CTSB

RTSB

R

*

R : 120

1/2W

POD (CN1)

+SD

-SD

+RD

-RD

*

Use twist shielded cables.

Memory

TYPE

Remarks

D

(data register)

0

X

(input register)

1

XW as word device

Y

(output register)

2

YW as word device

R

(auxiliary relay)

5

RW as word device

L

(link relay)

6

LW as word device

W

(link register)

7

F

(file register)

8

TN

(timer/current value)

9

Read only

CN

(counter/current value)

10

Read only

TS

(timer/contact)

11

Read only

CS

(counter/contact)

12

Read only

Advertising