13 - 23

13. OPTIONS AND AUXILIARY EQUIPMENT

13.2.2 No-fuse breakers, fuses, magnetic contactors

Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.

Fuse

Servo amplifier

No-fuse breaker

Class

Current [A]

Voltage [V]

Magnetic contactor

MR-E-10A

30A frame 5A

K5

10

MR-E-20A

30A frame 5A

K5

10

MR-E-40A

30A frame 10A

K5

15

MR-E-70A

30A frame 15A

K5

15

MR-E-100A

30A frame 15A

K5

15

S-N10

MR-E-200A

30A frame 20A

K5

15

AC250

S-N18

13.2.3 Power factor improving reactors

The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be
slightly lower than 90%.

3-phase

200 to 230VAC

NFB

FR-BAL

Servo amplifier

R

S

T

X

Y

Z

L

1

L

2

L

3

MC

1-phase

230VAC

NFB

FR-BAL

Servo amplifier

R

S

T

X

Y

Z

L

1

L

2

L

3

MC

W

W1

C

R X S Y T Z

H

5

D1 5

Installation screw

D

5

[Unit : mm]

Dimensions [mm (in) ]

Servo amplifier

Model

W

W1

H

D

D1

C

Mounting

screw size

Terminal

screw size

Weight

[kg (lb)]

MR-E-10A/20A

FR-BAL-0.4K

135 (5.31) 120 (4.72) 115 (4.53)

59 (2.32)

45 (1.77)

7.5 (0.29)

M4

M3.5

2.0 (4.4)

MR-E-40A

FR-BAL-0.75K 135 (5.31) 120 (4.72) 115 (4.53)

69 (2.72)

57 (2.24)

7.5 (0.29)

M4

M3.5

2.8 (6.17)

MR-E-70A

FR-BAL-1.5K

160 (6.30) 145 (5.71) 140 (5.51)

71 (2.79)

55 (2.17)

7.5 (0.29)

M4

M3.5

3.7 (8.16)

MR-E-100A

FR-BAL-2.2K

160 (6.30) 145 (5.71) 140 (5.51)

91 (3.58)

75 (2.95)

7.5 (0.29)

M4

M3.5

5.6 (12.35)

MR-E-200A

FR-BAL-3.7K

220 (8.66) 200 (7.87) 192 (7.56)

90 (3.54)

70 (2.76)

10 (0.39)

M5

M4

8.5 (18.74)