3. SIGNALS AND WIRING

(2) For 1-phase 230VAC power supply

Power supply
1-phase 230VAC

Emergency stop

Servo-on

Servo amplifier

Trouble

Emergency
stop

External

power

supply

24VDC

RA

OFF

ON

MC

MC

SK

NFB

MC

L

1

L

2

L

3

EMG

SON

SG

VIN

ALM

SG

RA

(Note)

CNP1

P

D

C

Note: To use the built-in regenerative resistor, be sure to connect across P and D of the power supply connector (CNP1).

3.7.2 Terminals

Refer to Section 11.1 (4) for the signal arrangement.

Connected terminal

(Application)

Symbol

Description

Supply L

1

, L

2

and L

3

with the following power:

For 1-phase 230VAC, connect the power supply to L

1

/L

2

and leave L

3

open.

L

1

Servo amplifier

Power supply

MR-E-10A to

70A

MR-E-100A/

200A

L

2

3-phase 200 to 230VAC,
50/60Hz

L

1

L

2

L

3

1-phase 230VAC,
50/60Hz

L

1

L

2

Power supply

L

3

U

V

Servo motor output

W

Connect to the servo motor power supply terminals (U, V, W).

P

C

Regenerative brake

option

D

To use the built-in regenerative brake resistor of the servo amplifier, connect the
wiring across P-D of the power supply connector (CNP1).
When using the regenerative brake option, always remove the wiring from across
P-D and connect the regenerative brake option across P-C.
Refer to Section 13.1.1 for details.

Protective earth (PE)

Connect this terminal to the protective earth (PE) terminals of the servo motor
and control box for grounding.