2 installation direction and clearances, Installation, Caution – MITSUBISHI ELECTRIC MR-E- A/AG User Manual

Page 29: Control box

Advertising
background image

2 - 2

2. INSTALLATION

2.2 Installation direction and clearances

CAUTION

The equipment must be installed in the specified direction. Otherwise, a fault may

occur.

Leave specified clearances between the servo amplifier and control box inside

walls or other equipment.

(1) Installation of one servo amplifier

MODE

CN3

SET

CN1

CN2

CNP2

CNP1

L3

L

2

L1

D

C

P

W

V

U

CH

A

R

G

E

MITSUBISHI
MR-

Control box

Control box

10mm
(0.4 in.)
or more

10mm
(0.4 in.)
or more

40mm
(1.6 in.)
or more

Servo
amplifier

40mm
(1.6 in.)
or more

Wiring clearance

Top

Bottom

(2.8 in.)

70mm

(2) Installation of two or more servo amplifiers

Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.

MODE

CN3

SET

CN1

CN2

CNP2

CNP1

L3

L

2

L1

D

C

P

W

V

U

CH

A

R

G

E

MITSUBISHI
MR-

MODE

CN3

CN1

CN2

CNP2

CNP1

L3

L

2

L1

D

C

P

W

V

U

CH

A

R

G

E

MITSUBISHI
MR-

SET

Control box

30mm
(1.2 in.)
or more

30mm
(1.2 in.)
or more

10mm
(0.4 in.)
or more

40mm
(1.6 in.)
or more

100mm
(4.0 in.)
or more