Signals and wiring – MITSUBISHI ELECTRIC MR-E- A/AG User Manual

Page 46

Advertising
background image

3 - 15

3. SIGNALS AND WIRING

Control

mode

Signal

Symbol

Connec-

tor pin

No.

Functions/Applications

I/O

division

P

S

Emergency stop

EMG

CN1-8

Disconnect EMG-SG to bring the servo motor to emergency stop
state, in which the servo is switched off and the dynamic brake is
operated.
Connect EMG-SG in the emergency stop state to reset that state.

DI-1

Clear

CR

CN1-5

Connect CR-SG to clear the position control counter droop pulses on
its leading edge. The pulse width should be 10ms or more.
When the parameter No.42 setting is " 1 ", the pulses are always
cleared while CR-SG are connected.

DI-1

Electronic gear
selection 1

CM1

When using CM1 and CM2, make them usable by the setting of
parameters No. 43 to 48.
The combination of CM1-SG and CM2-SG gives you a choice of four
different electronic gear numerators set in the parameters.
CM1 and CM2 cannot be used in the absolute position detection
system.

DI-1

(Note) Input signals

CM2

CM1

Electronic gear namerator

0

0

Parameter No. 3

0

1

Parameter No. 69

1

0

Parameter No. 70

1

1

Parameter No. 71

Electronic gear
selection 2

CM2

Note.0: CM1/CM2-SG off (open)

1: CM1/CM2-SG on (short)

DI-1

Gain changing

CDP

When using this signal, make it usable by the setting of parameter
No. 43 to 48.
Connect CDP-SG to change the load inertia moment ratio into the
parameter No. 61 setting and the gain values into the values
multiplied by the parameter No. 62 to 64 settings.

DI-1

Control change

LOP

<Position/internal speed control change mode>
Used to select the control mode in the position/internal speed
control change mode.

DI-1

(Note) LOP

Control mode

0

Position

1

Internal speed

Note.0: LOP-SG off (open)

1: LOP-SG on (short)

Refer to

Functions/

Appli-

cations.

Forward rotation
pulse train
Reverse rotation
pulse train

PP

NP

PG

NG

CN1-23

CN1-25

CN1-22

CN1-24

Used to enter a command pulse train.

In the open collector system (max. input frequency 200kpps):

Forward rotation pulse train across PP-SG
Reverse rotation pulse train across NP-SG

In the differential receiver system (max. input frequency 500kpps):

Forward rotation pulse train across PG-PP
Reverse rotation pulse train across NG-NP

The command pulse train form can be changed using
parameter No. 21.

DI-2