15 - 61

15. MR-E- AG SERVO AMPLIFIER COMPATIBLE WITH ANALOG INPUT

15.6.2 Alarms and warning list

POINT

Configure up a circuit which will detect the trouble (ALM) signal and turn
off the servo-on (SON) signal at occurrence of an alarm.

When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to Section 10.2.2 or 10.2.3 and take the appropriate action.
Set " 1" in parameter No. 49 to output the alarm code in ON/OFF status across the corresponding
pin and SG. Warnings (AL.E0 to AL.E9) have no alarm codes. Any alarm code is output at occurrence of
the corresponding alarm. In the normal status, the signals available before alarm code setting (CN1-12:
ZSP, CN1-11: RD, CN1-10: SA) are output.
The alarms marked in the alarm deactivation column can be deactivated by the corresponding
operations.

(Note 2) Alarm code

Alarm deactivation

Display

CN1-10

pin

CN1-11

pin

CN1-12

pin

Name

Power

OFF

ON

Press

"SET" on

current

alarm

screen.

Alarm

reset

(RES)

signal

AL.10

0

1

0

Undervoltage

AL.12

0

0

0

Memory error 1

AL.13

0

0

0

Clock error

AL.15

0

0

0

Memory error 2

AL.16

1

0

1

Encoder error 1

AL.17

0

0

0

Board error

AL.19

0

0

0

Memory error 3

AL.1A

1

0

1

Motor combination error

AL.20

1

1

0

Encoder error 2

AL.24

0

0

1

Main circuit error

AL.30

0

1

0

Regenerative error

(Note 1)

(Note 1)

(Note 1)

AL.31

0

1

1

Overspeed

AL.32

0

0

1

Overcurrent

AL.33

0

1

0

Overvoltage

AL.37

0

0

0

Parameter error

AL.45

1

1

0

Main circuit device overheat

AL.46

1

1

0

Servo motor overheat

AL.50

1

1

0

Overload 1

(Note 1)

(Note 1)

(Note 1)

AL.51

1

1

0

Overload 2

(Note 1)

(Note 1)

(Note 1)

AL.8A

0

0

0

Serial communication time-out error

AL.8E

0

0

0

Serial communication error

Alar

m

s

88888

0

0

0

Watchdog

AL.E0

Excessive regenerative warning

AL.E1

Overload warning

AL.E6

Servo emergency stop warning

Wa

rni

ngs

AL.E9

Undervoltage warning

Removing the cause of occurrence
deactivates the alarm
automatically.

Note: 1.

Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.

2. 0: off

1: on