13 - 31

13. OPTIONS AND AUXILIARY EQUIPMENT

(2) Selection example

Indicated below is an example of selecting a leakage current breaker under the following conditions:

SM

NV

Ig1

Iga

Ig2

Igm

Servo
amplifier
MR-E-40A

2mm

2

5m

2mm

2

5m

Servo motor
HC-KFE73

Use a leakage current breaker generally available.
Find the terms of Equation (13.2) from the diagram:

Ig1 20

1000

5

0.1 [mA]

Ig2 20

1000

5

0.1 [mA]

Ign 0 (not used)

Iga 0.1 [mA]

Igm 0.1 [mA]

Insert these values in Equation (13.2):

Ig 10 {0.1 0 0.1 1 (0.1 0.1)}

4.0 [mA]

According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/SW/CP/CW/HW series.