15. MR-E- AG SERVO AMPLIFIER COMPATIBLE WITH ANALOG INPUT

Class

No.

Symbol

Name and function

Initial

value

Unit

Setting

range

Control

mode

0000

Refer to
Name
and
function
column.

S

S

20

*OP2 Function selection 2

Used to select restart after instantaneous power failure,
servo lock at a stop in speed control mode, and slight vibration
suppression control.

0: Invalid
1: Valid

If the input power supply voltage
had reduced in the speed control
mode to stop the servo motor
due to the undervoltage alarm (AL.10)
but the supply voltage has return-
ed to normal, the servo motor can
be restarted by merely switching
on the start signal without resett-
ing the alarm.

Restart after instantaneous
power failure

Stop-time servo lock selection

The shaft can be servo-locked to
remain still at a stop in the internal
speed control mode.

0: Valid
1: Invalid

Slight vibration suppression control

Made valid when auto tuning selection is
set to "0400" in parameter No. 2.
Used to suppress vibration at a stop.

0: Invalid
1: Valid

Encoder cable communication system selection

Incorrect setting will result in an encoder alarm 1
(AL. 16) or encoder alarm 2 (AL. 20).

0: Two-wire type
1: Four-wire type

S T

Ex

pan

si

on

par

ame

te

rs

1

21

For manufacturer setting
Don’t change this value by anymeans.