Internal motor control (MCTRL)

3−105

l

EDSVS9332S−EXT EN 2.0

3.2.39.3

Torque limitation

Via the inputs MCTRL−LO−M−LIM and MCTRL−HI−M−LIM an external torque limitation can be set.
This serves to set different torques for the quadrants "driving" and "braking".

l

MCTRL−HI−M−LIM is the upper torque limit in [%] of the max. possible torque (C0057).

l

MCTRL−LO−M−LIM is the lower torque limit in [%] of the max. possible torque (C0057).

l

In case of quick stop (QSP) the torque limitation is deactivated.

(

Stop!

Only apply positive values to MCTRL−HI−M−LIM and negative values to
MCTRL−LO−M−LIM. Otherwise the speed controller may lose control and the drive
may rev up in an uncontrolled manner.