Mains failure control, Function library, Function blocks – Lenze EVS9332xS User Manual

Page 166: 40 mains failure control (mfail)

Advertising
background image

Function library

Function blocks

3.2.40

Mains failure control (MFAIL)

3−114

l

EDSVS9332S−EXT EN 2.0

3.2.40.2

Mains failure control

Integration of the function block into the signal flow of the controller

As an example, the function block is integrated into the basic configuration C0005 = 1000 (speed
control).

C0988/7

MFAIL−DC−SET

C0989/1

MFAIL−FAULT

MFAIL−RESET

C0982

C0971

C0972

C0978

MFAIL−ADAPT

C988/2

C0973

C0974

C0981

+

1

0

C0988/1

C0970

MFAIL−CONST

C988/3

C0980 Vp

Tn

MCRTL−
DCVOLT

C0989/2

MFAIL−THRESHOLD

C0975

C0988/4

MFAIL−NACT

C0976

C0988/5

MFAIL−SET

C0977

C0988/6

CTRL

MFAIL−I−RESET

MFAIL−NOUT

MFAIL−STATUS

MFAIL

+

MFAIL−N−SET

C0983

FIXED0%

C1472/19

C0472/18

NSET−NOUT

CMP2−OUT

DIGIN5

MCTRL−NACT

MCTRL−n−set

MCTRL−i−load

FIXED100%

MCTRL−NACT

9300kur024

Fig. 3−102

Linkage for the base configuration C0005 = 1000

1. Create speed setpoint path

·

C0970 = 5050 (NSET−NOUT to MFAIL−N−SET)

·

C0890 = 6100 (MFAIL−NOUT to MCTRL−N−SET)

2. Start value selection (here: act. speed value)

·

C0977 = 6100 (MFAIL−NOUT to MFAIL−SET)

3. Selection of setpoint source for DC−bus voltage (here: by

the freely connectable code FCODE C0472/19)

·

C0978 = 19539 (C0472/19 to MFAIL−DC−SET)

4. Selection of source which activates the mains failure

control

·

see chapter 3.2.40.1

5. Adaptation of proportional gain and DC−bus voltage

controller

·

C0974 = 1006 (FIXED100% to MFAIL−CONST)

·

C0973 = 1000 (FIXED0% to MFAIL−ADAPT)

6. Achieve restart protection

·

C0976 = 6100 (MFAIL−NACT to MCTRL−NACT)

·

C0975 = 19538 (C0472/18 to MFAIL−THRESHLD)

·

First enter approx. 2 % under C0472/18 (reference: nmax C0011)

7. Connect reset input (here with terminal X5/E5

TRIP−RESET)

·

C0972 = 55 (DIGIN5 to MFAIL−RESET)

8. Enter all function blocks used (except for codes and digital inputs DIGIN) into free positions of the processing table in C0465.

)

Note!

All settings must be saved non−volatile in a parameter set under C0003.