42 monitor outputs of monitoring system (monit), Monitor outputs of monitoring system (monit), Function library – Lenze EVS9332xS User Manual

Page 175

Advertising
background image

Function library

Function blocks

3.2.42

Monitor outputs of monitoring system (MONIT)

3−123

l

EDSVS9332S−EXT EN 2.0

3.2.42

Monitor outputs of monitoring system (MONIT)

Purpose

The monitoring functions output digital monitor signals.

FB_monit

LU

OU

EER

..

..

..

..

P18

SD8

nErr

MONIT

Fig. 3−106

Monitor outputs of the monitoring system (MONIT)

Function

The MONIT outputs switch to HIGH level if one of the monitoring functions responds.

The digital monitor signals respond dynamically, i.e.

l

depending on the state of the monitoring function, but

l

independently of the selected fault reaction (e.g. TRIP).

Example

MONIT−LP1 (motor phase monitoring) responds if a cable disruption is detected in a motor
connection phase, although the fault reaction of LP1 is set to "Off" (C0597 = 3).

)

Note!

l

With appropriate signal conditioning, the MONIT outputs can be used to locate
the cause of malfunction (e.g. by storing the MONIT output signal via the FLIP
function block).

l

More detailed descriptions of the monitoring functions / error messages can be
found in the chapter "Troubleshooting and fault elimination".

Advertising