Function library, Working with function blocks, 3 connecting function blocks – Lenze EVS9332xS User Manual

Page 59: Condition: – default setting

Advertising
background image

Function library

Working with function blocks

3.1.3

Connecting function blocks

3−7

l

EDSVS9332S−EXT EN 2.0

Basic procedure

1. Select the configuration code of the function block input which is to be changed.

2. Determine the source of the input signal for the selected input

(e.g. from the output of another function block).

3. The function block input is assigned via a menu which contains only those signal sources

which are of the same type as the function block input to be assigned.

4. Select and confirm the signal source.

5. Remove undesired connections, if any.

– For this, select the corresponding signal assignment of the input via the configuration code

(e.g. FIXED0, FIXED1, FIXED0%, ...).

6. Repeat 1. to 5. until the desired configuration is set.

7. Save modified configuration in the desired parameter set.

Example

l

Condition:
– Default setting

l

Task:
– Square the analog signal of X6/3, X6/4 and output to X6/62.

l

Solution:
– You need the function blocks AIN2, ARIT2 and AOUT2.

+ −

*

/

x/(1−y)

C0600

x
y

ARIT2

ARIT2−OUT

C0602/1

"200%

C0602/2

ARIT2−IN1

ARIT2−IN2

C0601/1

C0601/2

62

AOUT1

C434/1

+

+

AOUT1−IN

AOUT1−GAIN

AOUT1−OFFSET

C0434/3

C0434/2

C0431

C0433

C0432

3

4

AIN2

+

+

AIN2−OUT

AIN2−GAIN

AIN2−OFFSET

C0409/1

C0409/2

C0407

C0408

C0108/1

C0109/1

C0027/2

C0026/2

Fig. 3−3

Example of a simple configuration