Ramp function generator, Value range of the output signal, Evaluation of the output signal – Lenze EVS9332xS User Manual

Page 196: Deactivation of the process controller, Function library, Function blocks

Advertising
background image

Function library

Function blocks

3.2.48

Process controller (PCTRL1)

3−144

l

EDSVS9332S−EXT EN 2.0

3.2.48.2

Ramp function generator

The setpoint PCTRL−SET is led via a ramp function generator with linear characteristic. Thus,
setpoint step−changes at the input can be transformed into a ramp.

100 %

0

tir

tif

Tir

Tif

t

RFG−OUT

[%]

w1

w2

T

ir

+ t

ir

100%

w2

* w1

T

if

+ t

if

100%

w2

* w1

Fig. 3−130

Acceleration and deceleration times of the ramp function generator

l

The ramps can be adjusted separately for acceleration and deceleration.

– Acceleration time t

ir

with C0332.

– Deceleration time t

if

with C0333.

l

PCTRL−INACT = HIGH

– The ramp function generator is immediately set to zero.

3.2.48.3

Value range of the output signal

l

The process controller operates in bipolar mode in the default setting.

– The output value is limited to

±100 %.

l

The function can be set to unipolar mode under C0337.

– The output value is limited to 0 ... +100 %.

3.2.48.4

Evaluation of the output signal

l

The output signal can be evaluated after the limitation block via PCTRL−INFLU.

– The process controller can be hidden or unhidden with this evaluation.

– The calcuation is done according to the following formula:

100 % (PCTRL−OUT) = 100 % * 100 % (PCTRL−INFLU).

3.2.48.5

Deactivation of the process controller

l

PCTRL−INACT = HIGH deactivates the process controller

– PCTRL−OUT is set to zero.

– The I−component is set to zero.

– The ramp function generator is set to zero.