Function library

Function blocks

3.2.57

Ramp function generator (RFG)

3−165

l

EDSVS9332S−EXT EN 2.0

3.2.57.1

Calculation and setting of the times T

ir

and T

if

The acceleration time and deceleration time refer to a change of the output value from 0 to 100 %.
The times T

ir

and T

if

to be set can be calculated as follows:

100 %

0

tir

tif

Tir

Tif

t

RFG1−OUT

[%]

w1

w2

T

ir

+ t

ir

100%

w2

* w1

T

if

+ t

if

100%

w2

* w1

Fig. 3−154

Acceleration and deceleration times of the ramp function generator

t

ir

and t

if

are the times desired for the change between w

1

and w

2

.The values for T

ir

and T

if

can be

set under C0671 and C0672.

3.2.57.2

Loading of the ramp function generator

The ramp function generator can be initialised with defined values via the inputs RFG1−SET and
RFG1−LOAD.

l

As long as the input RFG1−LOAD = HIGH, the input RFG1−SET is switched to the output.

l

If the input RFG1−LOAD = LOW, the ramp function generator accelerates/decelerates from this
value to its input value within the set T

i

times.