Page 160

Advertising
background image

Function library

Function blocks

3.2.39

Internal motor control (MCTRL)

3−108

l

EDSVS9332S−EXT EN 2.0

3.2.39.7

Angle controller

The angle controller is required to achieve angular synchronism and drift−free standstill.

)

Note!

Select a configuration with digital frequency coupling in C0005 since this serves to
link all important signals automatically. On this basis the system can be optimised.

Activating the angle controller

1. Configure a signal source with C0894, which provides the angular difference between setpoint

and actual angle (see "Digital frequency configuration under C0005).

2. Select a value > 0 at the MCTRL−PHI−LIM input.

3. Trigger the input MCTRL−PHI−ON with HIGH (e.g. with FIXED1).

4. Set the gain of the angle controller > 0 in C0254 (see chapter 3.2.39.4)

– Before setting C0254, select an as high as possible P−gain for the n−controller in C0070.

– Increase C0254 during operation until the drive shows the required control response.

Influence of angle controller

The output of the angle controller is added to the speed setpoint.

l

If the actual angle is lagging, the drive is accelerated

l

If the actual angle is leading the drive is decelerated until the required angular synchronism is
achieved.

The influence of the angle controller consists of:

l

Angular difference multiplied by the P−gain C0254

l

Additional influence via analog signal at MCTRL−P−ADAPT

l

Limitation of the angle controller output to

±MCTRL−PHI−LIM

Limitation of the angle controller output

This limits the max. speed−up of the drive at high angular differences.