40 mains failure control (mfail), Mains failure control (mfail), Function library – Lenze EVS9332xS User Manual

Page 163: Function blocks

Advertising
background image

Function library

Function blocks

3.2.40

Mains failure control (MFAIL)

3−111

l

EDSVS9332S−EXT EN 2.0

3.2.40

Mains failure control (MFAIL)

Purpose

If the supply voltage via L1, L2, L3 or +UG, −UG fails, the drive (drive network) can be decelerated
(braked) in a controlled way. Without this function, the drive (drive network) would coast.

C0988/7

MFAIL-DC-SET

C0989/1

MFAIL-FAULT

MFAIL-RESET

C0982

C0971

C0972

C0978

MFAIL-ADAPT

C988/2

C0973

C0974

C0981

+

-

1
0

C0988/1

C0970

MFAIL-CONST

C988/3

C0980 Vp

Tn

MCRTL-

DCVOLT

C0989/2

MFAIL-THRESHOLD

C0975

C0988/4

MFAIL-NACT

C0976

C0988/5

MFAIL-SET

C0977

C0988/6

CTRL

MFAIL-I-RESET

MFAIL-NOUT

MFAIL-STATUS

MFAIL

+

-

MFAIL-N-SET

C0983

Fig. 3−98

Mains failure control (MFAIL)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

MFAIL−N−SET

a

C0988/1

dec [%]

C0970

1

1000

Speed setpoint in [%] of C0011

MFAIL−ADAPT

a

C0988/2

dec [%]

C0973

1

1000

Dynamic adaptation of the proportional
gain of the U

Gset

controller in [%] of C0980

MFAIL−KONST

a

C0988/3

dec [%]

C0974

1

1000

Proportional gain of the U

Gset

controller in

[%] of C0980

MFAIL−THRESHOLD

a

C0988/4

dec [%]

C0975

1

1000

Restart threshold in [%] of C0011

MFAIL−NACT

a

C0988/5

dec [%]

C0976

1

1000

Comparison value for the restart threshold
in [%] of C0011

MFAIL−SET

a

C0988/6

dec [%]

C0977

1

1000

Speed start point for the deceleration in
[%] of C0011

MFAIL−DC−SET

a

C0988/7

dec [%]

C0978

1

1000

Voltage setpoint on which the DC bus
voltage is to be maintained, 100% =
1000V

MFAIL−FAULT

d

C0989/1

bin

C0971

2

1000

HIGH = activates the mains failure control

MFAIL−RESET

d

C0989/2

bin

C0972

2

1000

HIGH = reset

MFAIL−N−OUT

a

Speed setpoint in [%] of C0011

MFAIL−STATUS

d

HIGH = mains failure control active

MFAIL−I−RESET

d

HIGH = mains failure control active, the
drive is braking