Function library, Function blocks – Lenze EVS9332xS User Manual

Page 170

Advertising
background image

Function library

Function blocks

3.2.40

Mains failure control (MFAIL)

3−118

l

EDSVS9332S−EXT EN 2.0

Commissioning

The commissioning should be carried out with motors without load.

1. The drive can be started with a LOW−HIGH edge at X5/E5.

2. Set the acceleration time Tir:

– Set speed setpoint to 100%, operate controller with maximum speed.

– Inhibit controller via terminal X5/28 (you can also use any other controller inhibit source,

CINH) and measure deceleration time until standstill.

– Set approx. 1/10 of the deceleration time in C0982.

3. Setting the retrigger time

l

In case of mains failure detection by detecting the DC bus voltage level:

– Set measured deceleration time from item 2. under C0983.

l

In case of mains failure detection via an external system (e.g. supply module 934X):

– Under C0983, set the time in which the drive is to be continued to be braked in a controlled

way for short−term mains recovery.

4. Switch off supply voltage (mains or DC bus).

The oscilloscope should display the following characteristic:

t

UG

t1

t2

Abschaltschwelle LU

Abschaltschwelle OU

Einschaltschwelle Bremseinheit

t

n

0

0

Ansprechschwelle

CMP2-OUT

MFAIL-DC-SET

Fig. 3−103

Schematic representation with activated mains failure control (ideal characteristic)

t1 Mains failure
t2 Zero speed reached