Function blocks

3.2.40

Mains failure control (MFAIL)

3−112

l

EDSVS9332S−EXT EN 2.0

Range of functions

l

Mains failure detection

l

Mains failure control

l

Restart protection

l

Reset of the mains failure control

l

Dynamic adaptation of the control parameters

l

Fast mains recovery (KU)

l

Application examples

3.2.40.1

Mains failure control

A failure of the controller’s power section supply can be detected by

l

evaluating the DC−bus voltage or

l

an external system for mains failure detection (e.g. 934X module or voltage measuring relay).

It is possible to combine the two methods.

The type of the mains failure detection to be used depends on the drive system used.

DC−bus voltage evaluation

Use with single drives or multi−axis drives, which do not use external monitoring systems.

l

For this you can use a comparator (e.g. CMP2). Set the following signal combinations:

– C0688/1 = 5005 (MCTRL−DCVOLT to CMP2−IN1)

– C0688/2 = 19540 (free code C0472/20 to CMP2−IN2)

– C0971 = 10655 (CMP2−OUT to MFAIL−FAULT)

– Set function of the comparator CMP2 with C0685 = 3

Enter the function blocks CMP2 and MFAIL into free positions of the processing table in C0465.

C0989/1

MFAIL-FAULT

MFAIL-RESET

C0971

C0972

1
0

C0988/1

C0970

C0989/2

CTRL

MFAIL-NOUT

MFAIL-N-SET

MFAIL

C0686

C0687

C0689/1

CMP2

CMP2-OUT

CMP2-IN1

C0689/2

CMP2-IN2

C0688/1

C0688/2

C0685

C0472/20

MCTRL-DCVOLT

Fig. 3−99

Example of a mains failure detection with internal function blocks (section)