Function library

Function blocks

3.2.58

Sample and hold function (S&H)

3−166

l

EDSVS9332S−EXT EN 2.0

3.2.58

Sample and hold function (S&H)

Purpose

The FB can save analog signals. The saved value is also available after mains switching.

C0572

S&H1

S&H1-OUT

S&H1-IN

C0573

S&H1-LOAD

C0570

C0571

S&H

Fig. 3−155

Sample and hold function (S&H1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

S&H1−IN

a

C0572

dec [%]

C0570

1

1000

S&H1−LOAD

d

C0573

bin

C0571

2

1000

LOW = save

S&H1−OUT

a

Function

l

With S&H1−LOAD = HIGH the signal at the input S&H1−IN is switched to the output
S&H1−OUT.

l

With S&H1−LOAD = LOW the output S&H1−OUT is disconnected from the input S&H1−IN and
outputs the value which was last valid.

Saving in the case of mains disconnection:

l

Keep S&H1−LOAD at LOW level when disconnecting the supply voltage (mains, DC bus or
terminal 59).

l

Keep S&H1−LOAD at LOW level when connecting the supply voltage (mains, DC bus or
terminal 59).