Analog output via terminal 62/63 (AOUT)

3−29

l

EDSVS9332S−EXT EN 2.0

3.2.9

Analog output via terminal 62/63 (AOUT)

Purpose

AOUT1 and AOUT2 can be used as monitor outputs.

Internal analog signals can be output as voltage signals and be used e.g. as display values or
setpoints for slaves.

62

AOUT1

C434/1

+

+

AOUT1-IN
AOUT1-GAIN

AOUT1-OFFSET

C0434/3

C0434/2

C0431

C0433

C0432

Fig. 3−23

Analog output via terminal X6/62 (AOUT1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

AOUT1−IN

a

C0434/1

dec [%]

C0431

1

5001

AOUT1−GAIN

a

C0434/3

dec [%]

C0433

1

19510

AOUT1−OFFSET

a

C0434/2

dec [%]

C0432

1

19512

63

AOUT2

C439/1

+

+

AOUT2-IN
AOUT2-GAIN

AOUT2-OFFSET

C0439/3

C0439/2

C0436
C0438

C0437

Fig. 3−24

Analog output via terminal X6/63 (AOUT2)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

AOUT2−IN

a

C0439/1

dec [%]

C0436

1

5002

AOUT2−GAIN

a

C0439/3

dec [%]

C0438

1

19511

AOUT2−OFFSET

a

C0439/2

dec [%]

C0437

1

19513

Function

l

The value at input AOUTx−IN is multiplied by the value at input AOUTx−GAIN.

– The formula for the multiplication is: 100% * 100% = 100%.

l

The result of the multiplication is limited to ±200%.

l

The limited value is added to the value which is applied at input AOUTx−OFFSET.

– The formula for the addition is 50% + 10% = 60%. The result of the calculation is mapped

in such a way that 100% = 10 V.

l

The result of the addition is again limited to ±200%.

l

The result of the calculation is mapped in such a way that 100% = 10 V and is output as a
signal at terminal 62 or 63.