Rockwell Automation 2097-Vxxx Kinetix 350 Single-axis EtherNet/IP Servo Drive User Manual User Manual
Page 120
120
Rockwell Automation Publication 2097-UM002C-EN-P - December 2013
Chapter 7 Troubleshoot the Kinetix 350 Drive
Table 52 - Network Status Indicators
Table 53 - Port 1 Ethernet Communication Status Indicators
Status
Description
Off
No power or no IP address defined.
Alternating green/red
Self-test mode (power-up diagnostics).
Flashing green
Standby (device not configured, or connection not established.
Steady green
Normal operation. Device has at least one established connection.
Flashing red
Recoverable minor fault or connection timeout.
Steady red
Non-recoverable major fault or duplicate IP address.
IMPORTANT
Under some fault conditions, two reset commands can be required to clear
drive.
Status
Description
Off
No link partner present.
Flashing green
Link partner present, communication occurring.
Steady green
Link partner present, no communication occurring.