Chapter 2 Install the Kinetix 350 Drive System

Circuit Breaker/Fuse Specifications

While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.

Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.

Use class CC or T fast-acting current-limiting type fuses, 200,000 AIC,
preferred. Use Bussmann KTK-R, JJN, JJS or equivalent. Thermal-magnetic type
breakers preferred. The following fuse examples and Allen-Bradley circuit
breakers are recommended for use with Kinetix 350 drives.

Figure 2 - Fuse and Circuit Breaker (CB) Specifications

Drive Cat. No.

Drive
Voltage

Phase

UL Applications

IEC (non UL) Applications

Fuses

(Bussmann)

Miniature CB

(1)

Cat. No.

Motor Protection CB

(1)(2)

Cat. No.

DIN gG Fuses

Amps, max

Miniature CB

(1)

Cat. No.

Motor Protection CB

(1)

Cat. No.

2097-V31PR0-LM

120V

Single-phase

(voltage doubler)

KTK-R-20 (20 A)

1489-A1C200

140M-D8E-C20

20

1492-SP1D200

140M-D8E-C20

120/240V

Single-phase

KTK-R-10 (10 A)

1489-A1C100

140M-C2E-C10

10

1492-SP1D100

140M-C2E-C10

2097-V31PR2-LM

120V

Single-phase

(voltage doubler)

KTK-R-30 (30 A)

1489-A1C300

140M-F8E-C32

32

1492-SP1D300

140M-F8E-C32

120/240V

Single-phase

KTK-R-20 (20 A)

1489-A1C200

140M-D8E-C20

20

1492-SP1D200

140M-D8E-C20

2097-V32PR0-LM

240V

Single-phase

KTK-R-15 (15 A)

1489-A1C150

140M-D8E-C16

16

1492-SP1D150

140M-D8E-C16

2097-V32PR2-LM

KTK-R-20 (20 A)

1489-A1C200

140M-D8E-C20

20

1492-SP1D200

140M-D8E-C20

2097-V32PR4-LM

KTK-R-30 (30 A)

1489-A1C300

140M-F8E-C32

32

1492-SP1D320

140M-F8E-C32

2097-V33PR1-LM

120/240V

Single-phase

KTK-R-20 (20 A)

1489-A1C200

140M-D8E-C20

20

1492-SP1D200

140M-D8E-C20

240V

Three-phase

KTK-R-15 (15 A)

1489-A3C150

140M-D8E-C16

16

1492-SP3D150

140M-D8E-C16

2097-V33PR3-LM

120/240V

Single-phase

KTK-R-20 (20 A)

1489-A1C200

140M-D8E-C20

20

1492-SP1D200

140M-D8E-C20

240V

Three-phase

KTK-R-15 (15 A)

1489-A3C150

140M-D8E-C16

16

1492-SP3D150

140M-D8E-C16

2097-V33PR5-LM

120/240V

Single-phase

KTK-R-30 (30 A)

1489-A1C300

140M-F8E-C32

32

1492-SP1D300

140M-F8E-C32

240V

Three-phase

KTK-R-20 (20 A)

1489-A3C200

140M-D8E-C20

20

1492-SP3D200

140M-D8E-C20

2097-V33PR6-LM

120/240V

Single-phase

LPJ-40SP

N/A

140M-F8E-C32

40

N/A

140M-F8E-C32

240V

Three-phase

KTK-R-30 (30 A)

1489-A3C300

32

1492-SP3D300

2097-V34PR3-LM

480V

Three-phase

KTK-R-10 (10 A)

1489-A3C100

140M-C2E-C10

10

1492-SP3D100

140M-C2E-C10

2097-V34PR5-LM

KTK-R-10 (10 A)

1489-A3C100

140M-C2E-C10

10

1492-SP3D100

140M-C2E-C10

2097-V34PR6-LM

KTK-R-20 (20 A)

1489-A3C200

140M-D8E-C20

20

1492-SP3D200

140M-D8E-C20

(1) Bulletin 1492 circuit protection devices have lower short-circuit current ratings than Bulletin 140M devices. Refer to

http://ab.rockwellautomation.com/allenbradley/

productdirectory.page?

for product literature with specific short-circuit ratings.

(2) For UL applications, Bulletin 140M devices are applied as self-protected combination motor controllers.