Rockwell Automation Publication 2097-UM002A-EN-P - December 2013

Chapter 2 Install the Kinetix 350 Drive System

These illustrations show recommended bonding practices for painted panels,
enclosures, and mounting brackets.

Figure 4 - Recommended Bonding Practices for Painted Panels

Stud-mounting the Subpanel

to the Enclosure Back Wall

Subpanel

Star Washer

Nut

Back Wall of
Enclosure

Welded Stud

Use a wire brush to remove paint from
threads to maximize ground connection.

Use plated panels or scrape paint on
front of panel.

Nut

Star Washer

Welded Stud

Flat Washer

Stud-mounting a Ground Bus

or Chassis to the Subpanel

Scrape Paint

Flat Washer

If the mounting bracket is coated with
a non-conductive material (anodized
or painted), scrape the material around
the mounting hole.

Mounting Bracket or
Ground Bus

Subpanel

Subpanel

Nut

Nut

Star Washer

Flat Washer

Star Washer

Star Washer

Scrape paint on both sides of
panel and use star washers.

Tapped Hole

Bolt

Flat Washer

Ground Bus or
Mounting Bracket

If the mounting bracket is coated with
a non-conductive material (anodized
or painted), scrape the material around
the mounting hole.

Bolt-mounting a Ground Bus or Chassis to the Back-panel