Chapter 3 Kinetix 350 Drive Connector Data

Table 13 - Understanding Digital Input Functions

Table 14 - Digital Input Specifications

The digital inputs are optically isolated and sinks up to 24V DC. Electrical
details are shown in

Table 13

on

page 42

. You can set up the inputs for PNP

sourcing or NPN sinking.

Function

Description

Behavior

Enable

If the controller configuration specifies checking of the enable input, an
active state enables the power electronics to control the motor and an
inactive state prevents motion.
The drive generates an exception if the input is inactive when the
controller commands motion and has authorized checking. The drive
behavior in this situation is programmable.

By default drive enable input checking is enabled. If the checking is
authorized and the input is disabled the drive issues a Drive Enable
Start Inhibit and you are not be able to issue a Servo On instruction
from the controller.
To disable the Enable function:

Tie input to 24V DC

Write a Logix Designer message instruction that changes

enableInputChecking or Attribute 736 to zero, see instructions
on

page 100

Home

An active state indicates to a homing sequence that the referencing
sensor has been seen. Typically, a transition of this signal is used to
establish a reference position for the machine axis.

The function is always inactive unless armed by the controller.

Registration

An inactive-to-active transition (also known as a positive transition) or
active-to-inactive transition (also known as a negative transition) is
used to latch position values for use in registration moves.

Positive Over-travel

If the controller configuration specifies checking of the hardware over-
travel inputs, an inactive state indicates that a position limit has been
exceeded in the positive direction.
The drive generates an exception if the input is inactive when the
controller authorizes checking. The drive behavior in this situation is
programmable.

The function is always active.
To disable function:

Tie input to 24V

Set to only Fault Status

Negative Over-travel

If the controller configuration specifies checking of the hardware
overtravel inputs, an inactive state indicates that a position limit has
been exceeded in the negative direction.
The drive generates an exception if the input is inactive when the
controller authorizes checking. The drive behavior in this situation is
programmable.

Attribute

Value

Type

Active high, single-ended, current sinking

Functions

Enable, Home, Positive Over-travel, Negative Over-travel,
Registration

Input current (with 24V applied)

9 mA, max

On-state input voltage

4.2…24V @ 2…9 mA total

Off-state input voltage

0…2.5V

Pulse reject filtering (only Registration functions)

120 ns, nom

Pulse reject filtering, default (all other input functions, can be configured)

1.0 ms, nom

Propagation delay (only Registration function)

5 μs

Registration repeatability

200 ns

Input reaction time (Disable)

2 ms, max

Input reaction time (Enable, Positive Over-travel inputs)

2 ms, max