3. Click Hookup Tests category.

4. Type 2.0 as the number of revolutions for the test or another number more

appropriate for your application.

5.

6. Click the desired tab (Marker/Motor Feedback/Motor and Feedback).

In this example, the Motor and Feedback test is chosen.

7. Click Start.

This Test

Performs this Test

Marker

Verifies marker detection capability as you rotate the motor
shaft.

Motor Feedback

Verifies feedback connections are wired correctly as you rotate
the motor shaft.

Motor and Feedback

Verifies motor power and feedback connections are wired
correctly as you command the motor to rotate.

If drive ENABLE is

Then

Hard wired

Apply 24V DC

Not used

Disable enableInputChecking by using procedure on

page 100

ATTENTION: To avoid personal injury or damage to equipment, apply
only24V ENABLE signal to the axis you are testing.