Rockwell Automation Publication 2097-UM002C-EN-P - December 2013

55

Connect the Kinetix 350 Drive System Chapter 4

Isolation Transformer in Grounded Power Configurations

When you are using an isolation transformer, attach the chassis ground wire to
the neutral connection. This grounded neutral connection does the following:

Prevents the system from floating and thereby avoids any high voltages that

can otherwise occur, for example due to static electricity

Provides a solid earth path for fault conditions

Three-phase Power Wired to Single-phase Drives

This example illustrates grounded three-phase power wired to single-phase
Kinetix 350 drives when phase-to-phase voltage is within drive specifications.

Figure 30 - Single-phase Amplifiers on Three-phase Power (WYE)

(1) Contactors (MI, M2, and M3) can be optional. For more information, refer to Understanding the Machinery Directive, publication

SHB-900

. AC line filter is optional, but is required for CE compliance.

Feeder short circuit protection is not illustrated.

ATTENTION: If the supply transformer is an auto transformer (not
recommended), do not add a chassis earth ground. A chassis earth ground is
already included elsewhere in the system and adding another creates a short.

L1

L2

L3

IPD

L1
L2

IPD

L1
L2

IPD

L1
L2

L1

L2

L3

L2

L3

L1

Transformer

(WYE) Secondary

Grounded Neutral

Kinetix 350 Drives

(System A)

Single-phase AC Input

Input Fusing

M1

(1)

M2

(1)

M3

(1)

Ground Grid or

Power Distribution Ground

Bonded Cabinet

Ground Bus

Kinetix 350 Drives

(System B)

Single-phase AC Input

Kinetix 350 Drives

(System C)

Single-phase AC Input

Input Fusing

Input Fusing

2097-V32PRx-LM