Chapter 4 Connect the Kinetix 350 Drive System

If the entire channel is constructed of stranded cable (no fixed cable), then this is
the equation for calculating maximum length:

Maximum Length = (113-2N)/y, meters

where N = the number of connections in the channel

and y = the loss factor compared to fixed cable (typically 1.2…1.5).

Figure 43 - CompactLogix Ethernet Port Location

The Port 1 Ethernet connection is used for connecting to a Logix5000 controller
and configuring your Kinetix 350 drive.

Figure 44 - Ethernet Wiring Example - External Switch

The Ethernet ports are on

bottom of controller.

CompactLogix Controller Platform

1769-L33ERM Shown

2

3

5

4

1

R

W

P

CompactLogix Controller Platform

1769-L33ERM Shown

Personal Computer

1783-US05T

Stratix 2000

Switch

Kinetix 350 Drives