Agency Compliance

If this product is installed within the European Union and has the CE mark, the
following regulations apply.

For more information on electrical noise reduction, refer to the System Design
for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

CE Requirements

To meet CE requirements, these requirements apply:

Install an AC line filter (Bulletin 2090 or 2097) as close to the drive as

possible.

Use 2090 series motor power cables or use connector kits and terminate

the cable shields to the subpanel with clamp provided.

Use 2090 series motor feedback cables or use connector kits and properly

terminate the feedback cable shield. Drive-to-motor power and feedback
cables must not exceed 20 m (65.6 ft).

Install the Kinetix 350 system inside an enclosure. Run input power wiring

in conduit (grounded to the enclosure) outside of the enclosure. Separate
signal and power cables.

Segregate input power wiring and motor power cables from control wiring

and motor feedback cables. Use shielded cable for power wiring and
provide a grounded 360° clamp termination.

Refer to Appendix A on

page 129

for interconnect diagrams, including input

power wiring and drive/motor interconnect diagrams.

ATTENTION: Meeting CE requires a grounded system. The method of
grounding the AC line filter and drive must match. Failure to do this renders the
filter ineffective and can cause damage to the filter.

For grounding examples, refer to

Grounding Your Kinetix 350 Drive System

on

page 58

.