Three-phase power wired to three-phase drives – Rockwell Automation 2097-Vxxx Kinetix 350 Single-axis EtherNet/IP Servo Drive User Manual User Manual

Page 53

Advertising
background image

Rockwell Automation Publication 2097-UM002C-EN-P - December 2013

53

Connect the Kinetix 350 Drive System Chapter 4

Three-phase Power Wired to Three-phase Drives

These examples illustrate grounded three-phase power wired to three-phase
Kinetix 350 drives when phase-to-phase voltage is within drive specifications.

Figure 26 - Three-phase (400/480V) Power Configuration (WYE secondary)

Figure 27 - Three-phase (240V) Power Configuration (Delta secondary)

(1) Leakage current from the line filter, in this configuration, typically is higher than a balanced (center ground) configuration.

Figure 28 - Three-phase (240V) Power Configuration (Delta secondary)

(1) Leakage current from the line filter, in this configuration, typically is higher than a balanced (center ground) configuration.

L3

L2

L1

IPD

L3

L2

L1

E

L3

L2

L1

L3

L2

L1

Transformer (WYE) Secondary

Kinetix 350 Drives

Three-phase AC Input

Bonded Cabinet Ground Bus

Ground Grid or

Power Distribution Ground

AC Line

Filter

M1

Contactor

Input Fusing

Feeder and branch short circuit

protection is not illustrated.

2097-V34PRx-LM

IMPORTANT

For the 480V Kinetix 350 drives to meet proper voltage creepage and clearance
requirements, each phase voltage to ground must be less than or equal to 300V
AC rms. This means that the power system must use center grounded wye
secondary configuration for 400/480V AC mains.

L3

L2

L1

IPD

L3

L2

L1

E

L3

L2

L1

L3

L2

L1

Transformer (Delta) Secondary

Kinetix 350 Drives

Three-phase AC Input

AC Line

(1)

Filter

Bonded Cabinet Ground Bus

Ground Grid or Power Distribution Ground

M1

Contactor

Input Fusing

Feeder and branch short circuit

protection is not illustrated.

2097-V33PRx-LM

L3

L2

L1

IPD

L3

L2

L1

E

L3

L2

L1

L3

L2

L1

Transformer (Delta) Secondary

Kinetix 350 Drives

Three-phase AC Input

AC Line

(1)

Filter

Bonded Cabinet Ground Bus

Ground Grid or Power Distribution Ground

M1

Contactor

Input Fusing

Feeder and branch short circuit

protection is not illustrated.

2097-V33PRx-LM