92

9469200990 Rev C

Table 12. Bus Voltage Sensing Terminals

Terminal

Description

46 (BUS VA)

A-phase bus voltage sensing input

48 (BUS VB)

B-phase bus voltage sensing input

50 (BUS VC)

C-phase bus voltage sensing input

Analog Engine Sender Inputs

Inputs are provided for oil pressure, fuel level, and coolant temperature senders. For a listing of oil
pressure, fuel level, and coolant temperature senders that are compatible with the DGC-2020ES, refer to
the Engine Sender Inputs chapter. Analog engine sender input terminals are listed in Table 13.

Table 13. Sender Input Terminals

Terminal

Description

1 (FUEL)

Fuel level sender input

2 (SENDER COM)

Sender return terminal

52 (OIL)

Oil pressure sender input

53 (COOLANT)

Coolant temperature sender input

Magnetic Pickup Input

The magnetic pickup input accepts a speed signal over the range of 3 to 35 volts peak and 32 to 10,000
hertz. Magnetic pickup input terminals are listed in Table 14.

Table 14. Magnetic Pickup Input Terminals

Terminals

Description

31 (MPU–)

Magnetic pickup return input

32 (MPU+)

Magnetic pickup positive input

Contact Sensing Inputs

Contact sensing inputs consist of seven programmable inputs. The programmable inputs accept normally
open, dry contacts. Terminal 17 (BATT–) serves as the common return line for the programmable inputs.
While input 1 is programmed to recognize an emergency stop input by default, it can be programmed for
any function. Information about configuring the programmable inputs is provided in the Contact Inputs
chapter. Contact sensing input terminals are listed in Table 15.

Table 15. Contact Sensing Inputs

Terminal

Description

17 (BATT–)

Common return line for programmable contact inputs

3 (INPUT 1)

Programmable contact input 1 (ESTOP by default)

4 (INPUT 2)

Programmable contact input 2

5 (INPUT 3)

Programmable contact input 3

6 (INPUT 4)

Programmable contact input 4

7 (INPUT 5)

Programmable contact input 5

8 (INPUT 6)

Programmable contact input 6

9 (INPUT 7)

Programmable contact input 7

Terminals and Connectors

DGC-2020ES