180

9469200990 Rev C

Note

The maximum voltage that can be safely applied to the DGC-2020ES
is 576 V. The pickup range is higher so that when the low-line override
is used, and the scale factor is 0.5 or less, effective protection levels of
500 V can be reached with a scale factor of 0.5.

Underfrequency (81U) and Overfrequency (81O)

Pickup Range ................................... 45 to 66 Hz
Pickup Increment ............................. 0.1 Hz
Activation Delay Range .................... 0 to 30 s
Activation Delay Increment .............. 0.1 s
Inhibit Voltage Range ....................... 70 to 576 Vac (81U function only)

Overcurrent (50)

Pickup Range ................................... 0.18 to 1.18 Aac (1 A current sensing)

0.9 to 7.75 Aac (5 A current sensing)

Time Dial Range .............................. 0 to 7,200 s (fixed time curve)
Time Dial Increment ......................... 0.1

Phase Imbalance (47)

Pickup Range ................................... 5 to 100 Vac
Pickup Increment ............................. 1 Vac
Activation Delay Range .................... 0 to 30 s
Activation Delay Increment .............. 0.1 s

Logic Timers

Hours Setting Range ........................ 0 to 250
Hours Setting Increment .................. 1
Minutes Setting Range ..................... 0 to 250
Minutes Setting Increment ............... 1
Seconds Setting Range ................... 0 to 1,800
Seconds Setting Increment .............. 0.1
Accuracy...........................................

±15 ms

Communication Interface

USB

Specification Compatibility ............... USB 2.0
Data Transfer Speed ........................ 115,200 baud
Connector Type ................................ Mini-B jack

RDP-110

Minimum Wire Size .......................... 20 AWG
Maximum Wire Length ..................... 4,000 feet (1,219 meters)
Terminals.......................................... 11 (RDP TxD+), 10 (RDP TxD–)

CAN

Differential Bus Voltage .................... 1.5 to 3 Vdc
Maximum Voltage ............................ –32 to +32 Vdc with respect to negative battery terminal
Communication Rate ........................ 250 kb/s
Terminals.......................................... 14 (low), 13 (high), and 15 (shield)

Specifications