Oil Pressure

Metering Range ................................ 0 to 150 psi, 0 to 10.3 bar, or 0 to 1,034 kPa
Accuracy...........................................

±3% of actual indication or ±2 psi, ±0.12 bar, or ±12 kPa (subject to
accuracy of sender)

Display Resolution ........................... 1 psi, 0.1 bar, or 1 kPa

Coolant Temperature

Metering Range ................................ 32 to 410

°F or 0 to 204°C

Accuracy...........................................

±3% of actual indication or ±2° (subject to accuracy of sender)

Battery Voltage

Metering Range ................................ 6 to 32 Vdc
Accuracy...........................................

±3% of actual indication or ±0.2 Vdc

Display Resolution ........................... 0.1 Vdc

Engine RPM

Metering Range ................................ 0 to 4,500 rpm
Accuracy

* ......................................... ±2% of actual indication or ±2 rpm

Display Resolution ........................... 2 rpm

* When engine speed is below 2% of full-scale, reported rpm is 0.

Engine Run Time

Engine run time is retained in nonvolatile memory.
Metering Range ................................ 0 to 99,999 hours
Update Interval ................................. 6 min
Accuracy...........................................

±1% of actual indication or ±12 min

Display Resolution ........................... 1 minute

Maintenance Timer

Maintenance timer indicates the time remaining until genset service is due. Value is retained in
nonvolatile memory.
Metering Range ................................ 0 to 5,000 hours
Update Interval ................................. 6 min
Accuracy...........................................

±1% or actual indication or ±12 min

Display Resolution ........................... 1 minute

Fuel Level

Metering Range ................................ 0 to 100%
Accuracy...........................................

±3% (subject to accuracy of sender)

Display Resolution ........................... 1.0%

Generator Protection Functions

Overvoltage (59) and Undervoltage (27)

Pickup Range ................................... 70 to 1,000 Vac
Pickup Increment ............................. 1 Vac
Inhibit Frequency Range .................. 20 to 66 Hz (27 function only)
Activation Delay Range .................... 0 to 30 s
Activation Delay Increment .............. 0.1 s