Name

Description

Symbol

MTUSPDDMDSW

This logic element can be used to specify the Speed
Demand Source parameter value that is sent to an MTU
Engine ECU. When no input is true, the value sent to the
engine ECU is the value specified in the Speed Demand
Source setting in the ECU configuration setting. If an input
on this logic element is true, the selected Speed Demand
Source will be sent rather than the value specified by the
Speed Demand Source setting.

If multiple inputs are true at the same time, the input that is
closest to the top of the logic element symbol will specify the
Speed Demand Source parameter value that is sent to the
ECU.

Analog CAN: This input configures the MTU ECU to accept
speed bias requests over J1939 CAN Bus from the DGC-
2020ES.

Up Down ECU: This input configures the MTU ECU to
accept speed raise/lower commands via contact inputs on
the ECU.

Up Down CAN: This input configures the MTU ECU to
accept speed raise/lower commands via communications
over J1939 CAN Bus.

Analog ECU: This input configures the MTU ECU to accept
speed bias via bias voltage input connections on the ECU.

Frequency: This configures the MTU ECU to accept speed
commands via a frequency signal input on the ECU. The
mapping of input signal frequency to machine speed is
configured in a curve within the engine ECU.

No CAN Demand: This input configures the MTU ECU to
disregard all speed requests or speed raise/lower requests
from J1939 CAN Bus.

OFFMODE

When this input is true, the DGC-2020ES will switch to OFF
mode. This is a pulsed input. It does not need to be held
after the desired mode switch has occurred.

PRESTARTOUT

This element is used to drive the prestart output relay from
logic when the Prestart Output Relay configuration is set to
“Programmable”. When the Prestart Output Relay
configuration is set to “Programmable”, the prestart relay will
not close unless logic is used to drive this element. When
the Prestart Output Relay configuration is set to
“Predefined”, the prestart relay is closed according to the
predefined prestart functionality of the DGC-2020ES. When
the “Predefined” functionality is selected, the relay will not
respond to this element.

RDPPROGALM1

When true, this element illuminates the Fuel Leak/Sender
Failure
LED on the Remote Display Panel RDP-110. When
this element is connected in logic, it overrides all other
commands to the LED. Otherwise, the LED operates as
normal.

RDPPROGALM2

When true, this element illuminates the Sender Failure LED
on the Remote Display Panel RDP-110.

When this element

is connected in logic, it overrides all other commands to the
LED. Otherwise, the LED operates as normal.