Basler Electric DGC-2020ES User Manual

Page 129

Advertising
background image

9469200990 Rev C

121

Name

Description

Symbol

Output Objects

Physical
Outputs
OUT1 – OUT4

Physical Outputs 1 through 4.

Remote Outputs
OUT5 – OUT28

Remote Outputs 5 through 28.
(Available when an optional CEM-2020 is connected.)

Alarms

Auto Restart
Fail

True after the Automatic Restart function fails to restart
the generator.

Battery Charger
Fail

True when the Battery Charger Fail function is
configured as an alarm and the activation delay has
expired.

Coolant Level
Sender Fail

True when a low coolant level error status code is
received from the ECU. CAN Bus must be enabled.

Coolant Temp
Sender Fail

True when the Coolant Temp Sender Fail is configured
as an alarm and the activation delay has expired.

ECU Comm
Loss

True when communication to ECU has been lost.

ECU Shutdown

True when ECU has shut down the engine.

Emergency
Stop

True when the Emergency Stop button has been
pressed.

Fuel Leak

True when the Fuel Leak Detect function is configured
as an alarm and the activation delay has expired.

Fuel Level
Sender Fail

True when the Fuel Level Sender Fail is configured as
an alarm and the activation delay has expired.

Generator
Protection
27

True when the 27 element is configured as an alarm
and has tripped.

Generator
Protection
59

True when the 59 element is configured as an alarm
and has tripped.

Generator
Protection
47

True when the 47 element is configured as an alarm
and has tripped.

Generator
Protection
50

True when the 50 element is configured as an alarm
and has tripped.

Generator
Protection
81 Over

True when the 81 Over element is configured as an
alarm and has tripped.

Generator
Protection
81 Under

True when the 81 Under element is configured as an
alarm and has tripped.

DGC-2020ES

BESTlogic

Plus