Output contacts, Usb interface, Can interface – Basler Electric DGC-2020ES User Manual

Page 101

Advertising
background image

9469200990 Rev C

93

Output Contacts

The DGC-2020ES has three sets of fixed-function output contacts: Pre, Start, and Run. The Pre contacts
supply battery power to the engine glow plugs, the Start contacts supply power to the starter solenoid,
and the Run contacts supply power to the fuel solenoid. Connections to the three sets of contacts are
made at terminals 19 through 24. The Pre, Start, and Run relay terminals are listed in Table 16.

Table 16. Fixed-Function Output Contact Terminals

Terminal

Description

19 (START)

Start output contact (Start solenoid)

20 (START)

21 (RUN)

Run output contact (Fuel solenoid)

22 (RUN)

23 (PRE)

Pre-start output contact (Glow plugs)

24 (PRE)

Four programmable output contacts are provided in two sets. Each set of two output contacts share a
common terminal. Programmable output contact terminals are listed in Table 17.

Table 17. Programmable Output Contact Terminals

Terminal

Description

25 (COM 1, 2)

Common connection for outputs 1 and 2

26 (OUT 1)

Programmable output 1

27 (OUT 2)

Programmable output 2

28 (COM 3, 4)

Common connection for outputs 3 and 4

29 (OUT 3)

Programmable output 3

30 (OUT 4)

Programmable output 4

USB Interface

A mini-B USB socket enables local communication with a PC running BESTCOMSPlus software. The
DGC-2020ES is connected to a PC using a standard USB cable equipped with a type A plug on one end
(PC termination) and a mini-B plug on the other end (DGC-2020ES termination).

CAN Interface

These terminals provide communication using the SAE J1939 protocol or the MTU protocol and provide
high-speed communication between the DGC-2020ES and an ECU on an electronically controlled engine.
Connections between the ECU and DGC-2020ES should be made with twisted-pair, shielded cable. CAN
interface terminals are listed in Table 18. For typical CAN connections, refer to the Typical Connections
chapter.

Table 18. CAN Interface Terminals

Terminals

Description

13 (CAN H)

CAN high connection

14 (CAN L)

CAN low connection

15 (SHIELD)

CAN drain connection

DGC-2020ES

Terminals and Connectors