Basler Electric DGC-2020ES User Manual

Page 139

Advertising
background image

9469200990 Rev C

131

Name

Description

Symbol

DPFMANREGEN

Diesel Particulate Filter Regeneration is forced manually
when the Set input is true.

DPFREGENINHIBIT

Diesel Particulate Filter Regeneration is inhibited when the
Set input is true.

ENGINERUN

The Start input starts the generator. No load is applied. The
breaker remains open. The Stop input stops the generator.
The DGC-2020ES only responds to this logic element when
in AUTO mode.

EPSSUPPLYINGLD

When this element is true and the generator is deemed
stable, the EPS Supplying Load LED, on the front panel, is
illuminated.
Under normal operation, the DGC-2020ES indicates that it
is supplying load when the generator is deemed stable and
the generator current is above a percentage of CT primary
current (typically 3%). The generator current requirement for
supplying load indication may be bypassed by setting this
element true. This is useful for testing purposes or in cases
where the generator supplies load at a current level which
falls below the requirement.
A cool-down cycle is performed when the DGC-2020ES is in
auto mode, is indicating that it is supplying load (whether
driven by logic or generator current), and the ATS input is
removed.

ESTOP

When this element is true, an Emergency Shutdown alarm
is annunciated and the Emergency Stop LED on the RDP-
110 is illuminated.

EXTSTARTDEL

If the Set input is true while the DGC-2020ES is in the Pre
Start state, the DGC-2020ES will remain in the Pre Start
state until the Set input is false.

DGC-2020ES

BESTlogic

Plus

Advertising