Basler Electric DGC-2020ES User Manual

Page 133

Advertising
background image

9469200990 Rev C

125

Name

Description

Symbol

Hi Coolant
Temp

True when the High Coolant Temp Pre-Alarm threshold
has been exceeded.

High Exhaust
Temperature

True when Diesel Particulate Filter (DPF) lamp status
broadcast over CAN Bus indicates high exhaust
temperature.

High Fuel Level

True when the High Fuel Level Pre-Alarm settings
have been exceeded.

Low Battery
Voltage

True when the Low Battery Voltage Pre-Alarm settings
have been exceeded.

Low Coolant
Level

True when the Low Coolant Level function is
configured as a pre-alarm and the activation delay has
expired. In addition, true when CAN Bus is enabled
and the Low Coolant Level Pre-Alarm threshold has
been exceeded.

Low Coolant
Temp

True when the Low Coolant Temp Pre-Alarm threshold
has been exceeded.

Low Fuel Level

True when the Low Fuel Level Pre-Alarm threshold has
been exceeded.

Low Oil
Pressure

True when the Low Oil Pressure Pre-Alarm threshold
has been exceeded.

Mains Breaker
Close Fail

True when a mains breaker close fail pre-alarm occurs.
The pre-alarm occurs when the DGC-2020ES has
issued a mains breaker close output but does not
receive a mains breaker status input that indicates the
breaker has closed before the breaker close wait time
has expired.

Mains Breaker
Open Fail

True when a mains breaker open fail pre-alarm occurs.
The pre-alarm occurs when the DGC-2020ES has
issued a mains breaker open output but does not
receive a mains breaker status input that indicates the
breaker has opened before the breaker close wait time
has expired.

Mains Fail
Return Failed

True when a mains fail return fail pre-alarm has
occurred. The pre-alarm occurs when the DGC-2020 is
attempting to transfer from generator power to mains
power after mains returns, but has not returned to the
mains from the generator before the Mains Fail Return
Delay has expired.

Mains Fail
Transfer Failed

True when a mains fail transfer fail pre-alarm occurs.
The pre-alarm occurs when the DGC-2020ES is
configured for mains fail transfers, but has not
transferred to the generator from the utility before the
Mains Fail Max Transfer Time has expired. It remains
true until the pre-alarm is cleared by pressing the
Reset button on the front panel.

Maintenance
Interval

True when the Maintenance Interval Pre-Alarm
threshold has been exceeded.

DGC-2020ES

BESTlogic

Plus

Advertising