Real-time clock, Liquid crystal display (lcd), Type tests – Basler Electric DGC-2020ES User Manual

Page 189

Advertising
background image

9469200990 Rev C

181

Notes

1.

If the DGC-2020ES is providing one end of the J1939 bus, a 120

Ω, ½ watt

terminating resistor should be installed across terminals 14 (CANL) and 13
(CANH).

2.

If the DGC-2020ES is not part of the J1939 bus, the stub connecting the
DGC-2020ES to the bus should not exceed 914 mm (3 ft) in length.

3.

The maximum bus length, not including stubs, is 40 m (131 ft).

4.

The J1939 drain (shield) should be grounded at one point only. If
grounded elsewhere, do not connect the drain to the DGC-2020ES.

Real-Time Clock

Clock has leap year and selectable daylight saving time correction. Backup capacitor and backup battery
sustain timekeeping during losses of DGC-2020ES operating power.
Resolution ........................................ 1 s
Accuracy...........................................

±1.73 s/d at 25°C

Clock Holdup

Battery Holdup Time ........................ Approximately 10 yrs

Liquid Crystal Display (LCD)

Display ............................................ 128 by 64 dot pixels LCD with LED Backlight
Operating Temperature .................... –40 to +70

°C (–40 to +158°F)

Storage Temperature ....................... –40 to +80

°C (–40 to +176°F)

LCD Heater

The ambient temperature is monitored by a temperature sensor located near the LCD inside the DGC-
2020ES. The LCD heater turns on when the ambient temperature falls below 0

°C (32°F). The heater turns

off when the ambient temperature rises above 5

°C (41°F). This range of operation implements 5°C (9°F)

of hysteresis between heater turn-on and turn-off.

Type Tests

Shock and Vibration ......................... EN60068-2-6
Dielectric Strength ............................ IEC 255-5
Impulse ............................................ EN60664-1
Transients......................................... EN61000-4-4
Static Discharge ............................... EN61000-4-2

Shock

Withstands 15 G in three perpendicular planes.

Vibration

Tested in three mutually perpendicular planes for 8 hours over the following ranges:
3 to 25 Hz at 1.6 mm (0.063 inches), peak amplitude
25 to 2,000 Hz at 5G

DGC-2020ES

Specifications