Setting the time and date, Real-time clock specifications – Basler Electric DGC-2020ES User Manual

Page 176

Advertising
background image

168

9469200990 Rev C

Table 31. Settings for Clock

Setting

Range

Increment

Unit

Default

UTC Offset

–1,440 to 1,440

1

minutes

–6

DST Configuration

Floating Dates or Fixed Dates

n/a

n/a

Disabled

Start/End Time

Reference

Respective to Local Time or

Respective to UTC Time

n/a

n/a

Respective to

Local Time

Bias Setup (Hour)

–12 to 12

1

hours

Disabled

Bias Setup (Minute)

–59 to 59

1

minutes

0

Clock Not Set

Warning

Disable or Enable

n/a

n/a

Disable

Setting the Time and Date

Time and date settings are made through BESTCOMSPlus on the Real Time Clock screen (Figure 87) of
the Metering Explorer. Settings can also be made through the front panel.

Figure 87. Metering Explorer, Real Time Clock Screen

Real-Time Clock Specifications

Resolution ................................................................. 1 s

Accuracy....................................................................

±1.73 s/d at 25°C

Clock Holdup
Capacitor Holdup Time ............................................. Up to 24 hours depending on conditions
Battery Holdup Time ................................................. Approximately ten years depending on conditions

Timekeeping

DGC-2020ES