Figure 76. Settings Explorer, CAN Bus, ECU Setup

Remote Display Panel (optional)

Applications that require remote annunciation can use Basler Electric’s Remote Display Panel. This
device provides remote indication of many pre-alarm and alarm conditions.

Remote Display Panel connections are made at 10 (RDP TxD–), 11 (RDP TxD+), 17 (BATT–), and 18
(BATT+).

The following pre-alarm conditions are indicated by LEDs on the Remote Display Panel:

High coolant temperature

Low coolant temperature

Low oil pressure

Low fuel level

Weak battery

Battery overvoltage†

Battery charger failure

∗†

The following alarm conditions are indicated by LEDs and an audible alarm on the Remote Display Panel:

Low coolant level

High coolant temperature

Low oil pressure

Overcrank

Overspeed

Emergency stop activated

Fuel leak/Sender failure

∗†

Sender failure†

∗ This can be configured in the DGC-2020ES as None, Alarm, or Pre-alarm. See the Contact Inputs
chapter for more information. The LED on the Remote Display Panel illuminates when the input that is
assigned to the programmable function is closed, whether the function is configured as None, Alarm, or
Pre-alarm.

† This LED can be reprogrammed in the DGC-2020ES to suit the needs of a particular application. The
condition listed above is annunciated by default.